background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

SLR-E-IS_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

•  Conventional technology
•   Optional connection of remote 

indicator

•   Extremely fl at design
•   Function testable with test gas
•   ATEX certifi ed

Specifi cations

Ignition protection 

intrinsically safe

Ex classifi cation 

EEx ia IIC T5

Current consumption at 24V 

typ. 50µA (quiescent)

Ambient temperature 

-10°C to +55°C

Relative humidity 

10 – 95% (no condensation)

Dimensions ø × H (incl. base) 

100 × 46 (mm)

Colour 

cream

Weight 

115g

Approval 

BAS01ATEX1281

 

LPCB 164a

Order number 

241090

Order name 

IS Optical Smoke Detector/Conv. SLR-E-IS

The Intrinsically Safe Optical Smoke Detector SLR-E-IS 

uses  the  scattered  light  principle  and  was  developed 

for the detection of smoke particles in explosion-prone 

rooms. 

The modern design of the sensing chamber al-

lows to reliably evaluate the characteristics of fi re.

Conventional technology is used for alarm  transmission 

to the fi re detection control panel. In conjunction with the 

Safety Barrier ES58-2, the detector reaches the  given 

Ex classifi cation. The two LEDs with 360°  visibility indi-

cate the activated condition of the detector. By means 

of an auxiliary module, the connection to an ADM loop 

is possible.

A detector function test can be conducted by using test 

gas. The detector is attached to the IS Detector Base 

YBN-R/4IS.

Reviews: