The  Network  Redundant  Alarm  Converter  NNU5-1  is 

required  in  the  network  fi re  detection  control  panel 

 BCnet216  for  the  alarm  transmission  according  to 

ÖNORM F 3000. It has to be installed in every sectional 

control panel that is connected to the transmitting de-

vice to the fi re brigade. The componentry guarantees 

the alarm transmission to a transmitting device despite 

multiple line failures in the GSSnet.

•   Monitors up to 126 members of 

a Fire Detection Control Panel 

BCnet216

•   Circular redundant alarm line 

monitored for wire breakage

•   Meets redundancy requirements of 

ÖNORM F 3000

•   Easy installation in fi re detection 

control panel Series BC216

Current consumption at 24V 

typ. 4mA

BCnet redundant alarm line 

2-core circular line

Line resistance  

max. 1k

Ω

Ambient temperature 

-5°C to +50°C

Dimensions L × W × H 

75 × 40 × 15 (mm)

Weight 

40g

Part No. 

214031

Order name 

Network Redundant Alarm Converter NNU5-1