Description

With the Detector Zone Extension MGE8-1 the fi re de-

tection  control  panel  Series  BC016  can  be  extended 

from  8  to  16  addressable  detector  zones.  Up  to  64 

detectors (addresses) per detector line can be indivi-

dually identifi ed with the aid of an address module. In 

the event of an alarm, the fi re detection control panel 

indicates the number of the detector that triggers the 

alarm fi rst.

Depending on the type of detector (manual call point, 

automatic fi re detector with or without alarm verifi cati-

on, fault message contacts as well as contacts for tech-

nical messages), the function of the detector zone can 

be set separately for each detector line. Each input of 

the Detector Zone Extension is protected against over-

voltage and thus provides high system stability.

•   Extends fi re detection control panels 

Series BC016 to 16 detector lines in 

addressable conventional technology

•   Individual detector addressing with 

optional address module

•   Individual setting of detector zone 

function

•   Lines monitored for wire breakage, 

short circuit, and short to earth

Specifi cations

Current consumption at 24V 

typ. 32mA (8 zones terminated, without detectors)

Line voltage 

typ. 20.0V

Line current 

typ. 3.8mA 

End-of-line resistance 

5.6k

Ω

 or 3,3k

Ω

 (depending on setup)

Line resistance 

max. 50

Ω

 per core

Ambient temperature 

-5°C to +50°C

Dimensions L × W × H 

100 × 65 × 15 (mm)

Weight 

80g

Part No. 

210110

Order name 

Detector Zone Extension MGE8-1