Building Safety. Building Security.

fi g. A

fi g. C

fi g. B

Description

Specifi cations

•   Manual call points for different 

applications

•  High range of radio transmission
•   2 frequency bands with

24 bidirectional data channels

•   Fault message when door is opened
•  Case according to EN 54-11/B
•   Communication with radio interfaces 

M500RFE-AS und M400RFE-AS

The  red  Manual  Call  Point  M400DKMR-AS  (fi g. A)  and 

the blue Manual Call Point M400DKMB-AS with lettering 

„HAUSALARM“  (fi g. B)  communicate  with  the  RF  Inter-

faces M500RFE-AS or M400RFE-AS via a secured ra-

dio protocol. The detectors are especially suitable for 

areas,  where  cabling  is  impossible  or  uneconomical.

The plastic case, which is designed in accordance with 

EN 54-11/B, is provided with an integrated antenna and 

accommodates the 3.6V lithium battery.

4 data channels in the frequency band 868MHz as well 

as 20 channels in the frequency band 434MHz are avai-

lable for the bidirectional data transmission. The avai-

lability of the channel is checked regularly. During the 

learning phase of the detector, i.e., when the detector 

is registered at the radio interface, a unique key, based 

on a choice of several million codes, is created, which 

allows the unambiguous identifi cation of the detector. 

Regular status messages, monitoring of the battery vol-

tage and the long life of the included batteries ensure 

the high reliability of the system.

A built-in LED optically indicates the activated condition 

of the detector. The hinged door can be opened up to 

an angle of 180° and it is provided with a replaceable 

pane of glass. If the detector has been activated, an 

integrated  locking  device  prevents  the  closing  of  the 

door. When the door is opened, the detector sends a 

fault message to the radio interface.

Operating voltage 

3.6V (lithium battery, battery life approx. 1.5 years)

Range of radio transmission (free air) 

300m

Frequency band 

868MHz or 434MHz

Ambient temperature 

0°C to +40°C

Dimensions W × H × D 

125 × 125 × 36 (mm)

Approval 

VdS G204103