A

Building Safety. Building Security.

•   Dual infrared sensor

according to EN 54-10, Class 1

•   Detection of open fl ames through 

fl ickering infrared radiation

•   High immunity to deceptive alarms
•  Selectable response delay
•   Relay contacts for alarm and fault
•  Integrated optical test function

Description

The Flame Detector 16581 responds to the fl ickering 

infrared radiation of open fl ames. Therefore, it is extre-

mely well suitable for the detection of fi res which are 

diffi cult to detect with common smoke detectors – for 

example, alcoholic fi res or gas fl ames.

The detector is ideal for the following applications:

  • Aviation and automotive industry

  • Paint shops

  • Warehouses

  • Textile industry

  • Waste treatment

With  two  independent  infrared  sensors  for  different 

wavelengths and with an intelligent evaluation logic, the 

detector can safely distinguish between alarm situati-

ons and deceptive alarms. Therefore, it is very insensiti-

ve to disturbance sources such as sunlight, fl uorescent 

lamps or electric arcs.

The detector complies with EN 54-10, Class 1, which 

means it is suitable to detect fl ames up to a distance 

of 25m.

The response delay of the detector can be selected in 

4 steps between 1 and 8s. An alarm and a fault conditi-

on is signalled via two dry relay contacts. Conventional 

technology  is  used  for  alarm  transmission  to  the  fi re 

detection control panel. The detector can be integra-

ted into an ADM loop by means of a conventional zone 

module.

A  simple  test  of  the  detector  can  be  carried  out  by 

means of the integrated optical self test function, which 

does not require additional tools. During this self test, 

a built-in infrared source simulates a fi re situation which 

activates the detector.

The detector has been designed for indoor use. The op-

tional Detector Mounting Bracket 7127 allows stepless 

horizontal and vertical adjustment for the easy adaptati-

on of the detector to the required monitoring area.

For use in explosion-hazardous areas, an Ex version of 

the fl ame detector is available on request.