A
Building Safety. Building Security.
• Addressable conventional technology
• Maximum temperature 57°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Sealed electronics
Description
The Thermal ROR Detector GD-55000-122 reacts to
temperature changes within defi ned periods of time,
up to a maximum temperature of 57°C. The intelligent
evaluation of these data allows the early detection of
spreading fi res. The detector complies with Class A1R
and can be used up to a room height of 7.5m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. By
means of the optional Address Module NG60-1, each
detector can be addressed individually. With that, the
activated detector can also be safely identifi ed directly
on the control panel.
The detector can be attached to various bases and it
can be protected against theft.
Specifi cations
Operating voltage
Supply through the detector line voltage
Current consumption
typ. 45µA (quiescent)
Alarm temperature
57°C (maximum-heat component)
Operating temperature
max. +50°C
Ambient temperature
-20°C to +90°C (no condensation or icing)
Relative humidity
0 – 95% (no condensation)
Dimensions ø × H
100 × 42 (mm)
Colour
white
Weight
80g
Approval
VdS G200059
Order number
242024