A

Building Safety. Building Security.

•  Addressable conventional technology
•   Individual detector identifi cation with 

optional address module

•   Allows for connection of external 

remote indicator

•   Anti-tamper locking feature on 

detector base

•  Double dust trap and insect screen
•   Function check by means of test 

magnet or test gas

Description

Specifi cations

The Optical Smoke Detector FC600/O is based on the 

IR light scattering principle and offers superior wide-

spectrum detection of smoke aerosols generated by 

the majority of fi res. A symmetrical detection chamber 

allows for optimal smoke sensitivity from all directions. 

Any alarm will be transmitted to the fi re detection pa-

nel in conventional technology. An individual detector 

identifi cation can be obtained with the optional Address 

Module NG58-1.

The detector is equipped with an LED indicator which 

is visible from all sides at any angle and thus facilitates 

easy identifi cation of the alarming detector. In addition, 

a remote indicator can also be connected.

An automatic drift compensation keeps the response 

sensitivity of the detector constant for a long period.

The double dust trap effectively protects the detector 

FC600/O against false alarms resulting from dust con-

tamination and ambient light. An insect screen prevents 

insects from interfering with the detection chamber.

Several types of detector bases are available to faci-

litate quick and easy installation. To prevent unautho-

rized removal of the detector, all detector bases are 

equipped with an anti-tamper locking feature.

A detector function test can be conveniently conducted 

by using either a test magnet or test gas.

Operating voltage 

10 – 30VDC (supply through detector line voltage)

Current consumption 

typ. 75µA (normal condition)

Ambient temperature 

-30°C to +70°C

Relative humidity 

max. 95% (no condensation)

Dimensions ø × h (without base) 

106 × 46 (mm)

Colour 

white

Weight 

80g

Approvals 

LPCB 603a/01

 

0832-CPD-0125

Order number 

241070

Order name 

Optical Smoke Detector/Conv./FC600 FC600/O