The  Thermal  Max  Detector  ECO1005T  recognises  a 

maximum temperature of 58°C as sign of fi re. It com-

plies with Class A2S and can be used up to a room 

height of 6m.

Addressable conventional technology is used for alarm 

transmission  to  the  fi re  detection  control  panel.  By 

means of the Address Module NG58-1, each detector 

can be addressed individually.

A  test  activation  of  the  detector  can  be  carried  out 

using the Remote Test Unit ECO1000RTU. The detec-

tor can be attached to various detector bases and it 

can be protected against theft.

•  Addressable conventional technology
•   Alarm temperature 58°C
•   Individual detector addressing by 

means of optional address module

•   Optional connection of remote 

indicator

•   Function testable with Remote Test 

Unit ECO1000RTU

Specifi cations

Operating voltage 

Supply through the detector line voltage

Current consumption 

typ. 75µA (quiescent)

Alarm temperature 

typ. 58°C

Operating temperature 

max. +45°C

Ambient temperature 

-30°C to +70°C

Relative humidity 

5 – 95% (no condensation)

Dimensions ø × H 

102 × 40.5 (mm)

Colour 

white

Weight 

70g

Approval 

VdS G201073

Order number 

242046

Order name 

Thermal Max Detector/Conv./1000/SS ECO1005T