Chapter 3 • ADM technology
Connection of detectors Labor Strauss
3.15
Programming of detectors, modules and signalling devices
This part of the document is intended for Fire Detection Control Panels Series BC216 and BC600.
In the case of the Fire Detection Control Panel Series BC600, the elements have to be selected in PAR-
SOFT by means of the exact type (for example
FI750/OT
).
For the Fire Detection Control Panels Series BC216, the types have to be selected according to the
tables below and the detailed information which the tables contains. For example, for a detector of type
FI750/OT, the element type
Optical/therm detector
is to be used in PARSOFT.
3.15.1
Parameterising detectors on the BC216
Type
Element type in PARSOFT Level
Mode
Sensitivity
241080 FI700/0
very high
O
2.0%/m
high
O
2.7%/m
normal
O
3.3%/m
low
O
4.0%/m
242080 FI700/T
Thermal detector
78C Max
241081 FI700/OT
Optical/therm detector
very high
O/T
2.0%/m / A1R
high
O/T
2.7%/m / A1R
normal
O/T
3.3%/m / A1R
low
O/T
4.0%/m / A1R
thermal
T
A1R
241086 FI750/0
Optical detector
very high
O
2.0%/m
high
O
2.7%/m
normal
O
3.3%/m
low
O
4.0%/m
242086 FI750/T
Thermal detector
78C Max
Class BS typ. 78°C
241087 FI750/OT
Optical/therm detector
very high
O/T
2.0%/m / A1R
high
O/T
2.7%/m / A1R
normal
O/T
3.3%/m / A1R
low
O/T
4.0%/m / A1R
thermal
T
A1R
Manual Call Point
Manual Call Point
245080
Manual Call Point
245081 MCP67
Manual Call Point
Art.No.
Optical detector
58C RoR
Class A1R typ. 58°C (RoR, MAX)
Class BS
1)
typ. 78°C
58C ROR – every level
58C RoR
Class A1R typ. 58°C (RoR, MAX)
58C ROR – every level
HxM/x/72/xx/xx
HME/FFFF/72/TT/LL
MCP
1)
Class BS applies from firmware version 1.70 on. Thermal detectors with an earlier firmware version comply with
class B in level „78C“. The firmware version can be found on the label on the bottom of the detector.
Connection-LST.odt / 2009 / AN9161298
200/190