Description

The Thermal Max Detector 4351E recognises a maxi-

mum temperature of 78°C as sign of fi re. It complies 

with Class BS and can be used up to a room height 

of 6m.

Addressable conventional technology is used for alarm 

transmission  to  the  fi re  detection  control  panel.  The 

detector addressing can be achieved in 2 ways:

•   A detector with an Address Module NG58-1 can be 

individually identifi ed by the suitable control panel.

•   An address, which has been stored in the detector 

by means of the Remote Programming and Test Unit, 

is displayed on the Zonal Display Unit S300ZDU.

A  test  activation  of  the  detector  can  be  carried  out 

using the Remote Test Unit ECO1000RTU. In addition 

to the test activation of the detector, the Remote Pro-

gramming and Test Unit S300RPTU can also be used 

to set and display the following detector parameters:

•  the detector address, and

•  the date of the previous maintenance.

The detector can be attached to various detector ba-

ses and it can be protected against theft.

•   Addressable conventional technology
•   Alarm temperature 78°C
•   Addressing by means of address 

module or detector parameterisation

•   Remote readout of detector condition
•   Function testable with Remote Test 

Unit ECO1000RTU

Specifi cations

Operating voltage 

Supply through the detector line voltage

Current consumption 

typ. 85µA (quiescent)

Alarm temperature 

78°C

Ambient temperature 

-30°C to +70°C (continuous operation)

Relative humidity 

5 – 95% (no condensation)

Dimensions ø × H 

102 × 43 (mm)

Colour 

cream

Weight 

75g

Approval 

VdS G202016

Order number 

242041

Order name 

Thermal Max Detector/Conv./300/SS 4351E