LST 16589 Specification Sheet Download Page 1

0832–CPD–0595

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

IR3-16589_DBL_LST_EN_0850.PDF • PAGE 1

A

Building Safety. Building Security.

Description

•   Triple infrared sensor

according to EN 54-10, Class 1

•   Detection of open fl ames through 

fl ickering infrared radiation

•   Very high immunity to deceptive 

alarms

•  Selectable response delay
•   Relay contacts for alarm and fault
•  Integrated optical test function

The Flame Detector 16589 responds to the fl ickering 

infrared radiation of open fl ames. Therefore, it is extre-

mely well suitable for the detection of fi res which are 

diffi cult to detect with common smoke detectors – for 

example, alcoholic fi res or gas fl ames.

The detector is ideal for the following applications:

  • Pharmaceutical industry

  • Paint shops

  • Warehouses

  • Nuclear facilities

  • Tunnels

With  three  independent  infrared  sensors  for  different 

wavelengths and with an intelligent evaluation logic, the 

detector can safely distinguish between alarm situati-

ons and deceptive alarms. Therefore, it is particularly 

insensitive  to  disturbance  sources  such  as  sunlight, 

fl uorescent lamps or electric arcs.

The detector complies with EN 54-10, Class 1, which 

means it is suitable to detect fl ames up to a distance 

of 25m.

The response delay of the detector can be selected in 

4 steps between 1 and 8s. An alarm and a fault conditi-

on is signalled via two dry relay contacts. Conventional 

technology  is  used  for  alarm  transmission  to  the  fi re 

detection control panel. The detector can be integra-

ted into an ADM loop by means of a conventional zone 

module.

A  simple  test  of  the  detector  can  be  carried  out  by 

means of the integrated optical self test function, which 

does not require additional tools. During this self test, 

a built-in infrared source simulates a fi re situation which 

activates the detector.

The detector has been designed for indoor and outdoor 

use. The optional Detector Mounting Bracket 7127 al-

lows stepless horizontal and vertical adjustment for the 

easy adaptation of the detector to the required monito-

ring area.

For use in explosion-hazardous areas, an Ex version of 

the fl ame detector is available on request.

Reviews: