Wire the terminals as shown below and refer to I 6 - I 10.
Frequency setting via 0 - 20 [mA] input
7.1.5
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive
group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
4
0 - 8
0
I/O
group
I11
[Filter time constant for I input]
10
0 - 9999
10
I12
[I input minimum current]
-
0 - 20
4
mA
I13
[Frequency corresponding to I12] -
0 - 400
0.00
Hz
I14
[I input max current]
-
0 - 20
20
mA
I15
[Frequency corresponding to I14] -
0 - 400
60.00
Hz
Select 4 in Frq code of Drive group.
Frequency is set via 0-20mA input between I and CM terminal.
Frequency setting via -10 - +10[V] voltage input + 0 -
7.1.6
20[mA] input
Group
Code
Parameter Name
Setting Range
Default
Unit
Drive
group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
5
0 - 8
0
Select 5 in Frq code of Drive group.
Override function available using Main/Auxiliary speed adjustment
Related code: I 2 - I 5, I 6 - I10, I11 - I15
►
Override function is to gain precise control and fast response by combining Main and
Auxiliary speed input. Fast response can be achieved by Main speed and precise
control can be accomplished by Aux. speed if the accuracy of Main/Aux speed is set
differently.
►
Follow the setting below when Main speed is given via 0 - 20mA with Aux. speed via V1
terminal (
–10 - 10V).
►
When override function is used, select the Main/Aux. speed according to loads used.
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...