Advanced functions
100
8.3 UP-DOWN Operation
Up-down storage function
8.3.1
Group
Code
Parameter Name
Setting Range Default Unit
Drive
group
Frq
[Frequency setting method]
8
0-8
0
I/O group
I17
[Multi-function input terminal P1
define]
0
0 - 30
0
I18
[Multi-function input terminal P2
define]
25
1
I19
[Multi-function input terminal
P3define]
15
2
I20
[Multi-function input terminal
P4define]
16
3
Function
group 1
F63
[Up-down frequency Save select] -
0-1
0
F64
[Up-down frequency storage]
-
0.00
Select 8 in Frq code of drive group
Select the terminal which uses as a up-down drive among multi-function input (P1-P4)
If you select P3 and P4 as an up-down drive terminal, select each 15 (frequency
increase command) and 16 (frequency decrease command) in the I19 and I20 of I/O
group.
If you select P2 terminal as an up-own save initial terminal, select 25 (up-down save
initialization) as above.
Up/down Save function: If F63, ‘Save up/down frequency’, is set to 1, the frequency
before the inverter was stopped or decelerated is saved in F64.
►
While up-down save operates, the user can initialize the saved up-down frequency by
setting multi-function input terminal as a up-down frequency save initialization.
F63 Save up/down frequency select
0 Remove
‘save up/down frequency’
1 Set
‘save up/down frequency’
F64 Save up/down frequency
Up/down frequency saved
►
If
‘Up/Down Save Frequency Initialization’ signal is input while the multi-function input
‘Up’ or ‘Down’ function is applied, this signal is ignored.
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...