Learning Protection Features
340
6.3.7 No Motor Trip
If an operation command is run when the motor is disconnected from the inverter output
terminal, a ‗no motor trip‘ occurs and a protective operation is performed by the system.
Group Code Name
LCD Display
Parameter
Setting
Setting
range
Unit
PRT
31
Operation for no motor
trip
No Motor Trip
0
None -
-
32
No motor trip current level No Motor Level
5
1
–100
%
33
No motor detection time
No Motor Time
3.0
0.1
–10
sec
No Motor Trip Setting Details
Code
Description
PRT-32 No Motor
Level,
PRT-33 No Motor Time
If the output current value [based on the rated current (BAS-13)] is
lower than the value set at PRT-32 (No Motor Level), and if this
continues for the time set at PRT-33
(No Motor Time), a ‗no motor
trip‘ occurs.
If BAS-
07 (V/F Pattern) is set to ‗1 (Square)‘, set PRT-32 (No Motor Level) to a value lower than
the factory default. Otherwise, a ‗no motor trip,‘ due to a lack of output current, will occur when
the ‗no motor trip‘ operation is set.
6.3.8 Broken Belt
It is a function to detect a problem in case that a Belt or Coupling is broken while a pump is
used.
Group Code Name
LCD Display
Parameter
Setting
Setting range
Unit
PRT
91
Set broken belt
function
BrokenBelt Sel
0 : None
0 None
-
1 Warning
2 Free Run
92
Function frequency of
broken belt
BrokenBelt
Freq
15.00
15.00~MaxFreq
Hz
Summary of Contents for H100
Page 14: ......
Page 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 27: ...Preparing the Installation 13 ...
Page 47: ...33 Installing the Inverter ...
Page 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Page 61: ...47 Installing the Inverter ...
Page 71: ...Learning to Perform Basic Operations 57 ...
Page 88: ...Learning to Perform Basic Operations 74 ...
Page 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Page 129: ...115 Learning Basic Features ...
Page 140: ...Learning Basic Features 126 ...
Page 148: ...Learning Basic Features 134 ...
Page 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Page 183: ...169 Learning Advanced Features ...
Page 184: ...Learning Advanced Features 170 PID Command Block ...
Page 185: ...171 Learning Advanced Features PID Feedback Block ...
Page 186: ...Learning Advanced Features 172 PID Output Block ...
Page 187: ...173 Learning Advanced Features PID Output Mode Block ...
Page 197: ...183 Learning Advanced Features ...
Page 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Page 202: ...Learning Advanced Features 188 EPID2 Control block ...
Page 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Page 244: ...Learning Advanced Features 230 ...
Page 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Page 362: ...Learning Protection Features 348 ...
Page 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Page 524: ...Table of Functions 510 ...
Page 533: ...Table of Functions 519 ...
Page 547: ...533 Troubleshooting ...
Page 585: ...Technical Specification 571 ...
Page 594: ...580 ...
Page 595: ...581 ...
Page 596: ...582 ...