Take caution on any safety accidents when operating the inverter with Automatic
Restart After Reset enabled as the motor will begin rotating as soon as the inverter is
reset from the terminal block or keypad after a trip occurs.
4.8 Setting Acceleration and Deceleration Times
4.8.1 Acc/Dec Time Based on Maximum Frequency
Acc/Dec time values can be set based on maximum frequency, not on inverter
operation frequency. To set Acc/Dec time values based on maximum frequency, set
bA. 08 (Acc/Dec reference) in the Basic group to 0 (Max Freq).
Acceleration time set at the ACC (acceleration time) code in the Operation group
(dr.03) refers to the time required for the inverter to reach the maximum frequency
from a stopped (0 Hz) state. Likewise, the value set at the DEC (deceleration time)
code in the Operation group (dr.04) refers to the time required to return to a stopped
state (0 Hz) from the maximum frequency.
Group
Code
Name
Setting
Setting Range
Unit
Operation
ACC Acceleration time
5.0
0.0
–600.0
sec
dEC Deceleration time
10.0
0.0
–600.0
sec
dr
20 Maximum frequency
60.00
40.00
–400.00
Hz
bA
08
Acc/Dec reference
frequency
0
Max Freq
0
–1
-
09 Time scale setting
1
0.1sec
0
–2
-
Acc/Dec Time Based on Maximum Frequency
– Setting Details
Code and
Features
Description
bA.08
Ramp T Mode
Set the parameter value to 0 (Max Freq) to setup Acc/Dec time based
on maximum frequency.
Configuration
Function
0
Max Freq
Set the Acc/Dec time based on maximum
frequency.
1
Delta Freq
Set the Acc/Dec time based on operating
frequency.
If, for example, maximum frequency is 60.00 Hz, the Acc/Dec times
are set to 5 seconds, and the frequency reference for operation is set
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...