4.4 Command Source Configuration
Various devices can be selected as command input devices for the G100 inverter.
Input devices available to select include keypad, multi-function input terminal, RS-485
communication and field bus adapter.
Group
Code
Name
Setting
Setting Range
Unit
Operation
drv
Command
Source
0
Keypad
0
–4
-
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Fieldbus
4.4.1 The Keypad as a Command Input Device
The keypad can be selected as a command input device to send command signals to
the inverter. This is configured by setting the drv (command source) code to 0
(Keypad). Press the [RUN] key on the keypad to start an operation, and the
[STOP/RESET] key to end it.
Group
Code
Name
Setting
Setting Range
Unit
Operation
drv
Command
Source
0
Keypad
0
–4
-
4.4.2 Terminal Block as a Command Input Device (Fwd/Rev
Run Commands)
Multi-function terminals can be selected as a command input device. This is
configured by setting the drv (command source) code in the Operation group to 1
(Fx/Rx-1). Select terminals for the forward and reverse operations from P1
–P5 multi-
function input terminals. Then select 1 (Fx) and 2 (Rx) respectively for 65
–69 (Px
terminal setting options) codes of the In group. This enables both terminals to be
turned on or off at the same time, constituting a stop command that will cause the
inverter to stop operation.
Group
Code
Name
Setting
Setting Range
Unit
Operation
drv
Command
Source
1
Fx/Rx-1
0
–4
-
In
65
–69
Px terminal
setting options
1
Fx
0
–52
-
2
Rx
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...