3.3.2 Frequency Reference Configuration
The following is an example to demonstrate configuring a frequency reference of
30.05 Hz from the first code in the Operation group.
Step
Instruction
Keypad Display
1
Ensure that the first code of the Operation group is
selected, and code 0.00 (Command Frequency) is
displayed.
2
Press the [ENT] key.
The default value "0.00" will be displayed and "0" in the
second decimal place will flash.
3
Press the [MODE] key 3 times to move to the tens' place
value.
"0" in the tens' place will flash.
4
To make the target value "30.05", press the [
▲] key to
change the tens' place value to "3."
5
Press the [MODE] key 2 times.
The "0" in the second decimal place will flash.
6
To make the target value "30.05", press the [
▲] key to
change the second decimal place value to "5", and then
press the [ENT] key.
The selected value will flash on the display.
7
Press the [ENT] key again to save the changes.
Flashing stops. The frequency reference has been
configured to 30.05 Hz.
Note
•
A flashing number on the display indicates that the keypad is waiting for an input from
the user. Changes will be saved when the [ENT] key is pressed while the number is
flashing. The setting change will be canceled if you press any other key.
•
The G100 inverter keypad display can display up to 4 digits. However, 5-digit figures
can be used and are accessed by pressing the [MODE] key, to allow keypad input.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...