To connect cables to the control terminals without using crimp terminals, refer to the
following illustration detailing the correct length of exposed conductor at the end of the
control cable.
Note
•
While making wiring connections at the control terminals, ensure that the total cable
length does not exceed 165 ft (50 m).
•
Ensure that the length of any safety related wiring does not exceed 100 ft (30m).
•
Use ferrite material to protect signal cables from electro-magnetic interference.
•
Take care when supporting cables using cable ties, to apply the cable ties no closer
than 6 inches from the inverter. This provides sufficient access to fully close the front
cover.
•
When making control terminal cable connections, use a small flat-tip screw driver (0.1
in wide (2.5 mm) and 0.015 in thick (0.4 mm) at the tip).
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...