6.3 Under load Fault Trip and Warning
Group Code
Name
Setting
Setting Range
Unit
Pr
04
Load level
setting
0
Normal Duty
-
-
25
Under load
warning
selection
1
Yes
0
–1
-
26
Under load
warning time
10.0
0
–600
sec
27
Under load fault
selection
1
Free-Run
-
-
28
Under load fault
time
30.0
0
–600
sec
29
Under load lower
limit level
30
10
–100
%
30
Under load
upper limit level
30
10
–100
%
Under Load Trip and Warning Setting Details
Code and
Features
Description
Pr.27 UL Trip Sel
Sets the occurrence of the under load trip. If set to 0 (None), the
underload fault trip is not detected. If set to 1 (Free-Run), the output is
blocked in an underload fault trip situation. If set to 2 (Dec), the motor
decelerates and stops when an underload trip occurs.
Pr.25 UL Warn
Sel
Sets the underload warning options. Set to 1 (Yes) and set the
multi-function output terminals (at OU-31 and 33) to 7
(UnderLoad). The warning signals are output when an underload
condition arises.
Pr.26 UL Warn
Time,
Pr.28 UL Trip
Time
The protection function operates when the underload level condition
explained above is maintained for a set warning time or fault trip time.
This function does not operate if energy-saving operation is activated
at Ad-50 (E-Save Mode).
Pr.29 UL LF
Level, Pr.30 UL
BF Level
•
Setting Heavy Duty
- Do not support Pr.29.
-
At Pr.30, the underload level is decided based on the motor’s
rated current.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...