Input and Output Open-phase Protection Setting Details
Code and
Features
Description
Pr.05 Phase Loss
Chk,
Pr.06 IPO V Band
Input and output phase protection can each be selected. When the dot
is displayed above the switch, the corresponding bit is set to on. When
it is below the switch, it is set to on.
Items
Bit On Status
Bit Off Status
Keypad
Configuration
Function
bit2
bit1
Output open-phase protection
Input open-phase protection
Initial values by each product on input voltage range during open-
phase are shown as below.
Items
Initial Value
Unit
0.4 kW
–2.2 kW (200 V/400 V)
15
V
4.0 kW
–7.5 kW (200 V/400 V)
13
V
6.2.2 External Trip Signal
Set one of the multi-function input terminals to 4 (External Trip) to allow the inverter to
stop operation by using external signals.
Grou
p
Code
Name
Setting
Setting
Range
Unit
In
65
–69
Px terminal setting
options
4
External Trip
-
-
87
Multi-function input
terminal selection
-
bit
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...