5.12 Energy Saving Operation
5.12.1 Manual Energy Saving Operation
If the inverter output current is lower than the current which is set at bA.14 (Noload
Curr), the output voltage must be reduced as low as the level set at Ad.51 (Energy
Save). The voltage before the energy saving operation starts will become the base
value of the percentage. Manual energy saving operation will not be carried out during
acceleration and deceleration.
Group Code
Name
Setting
Setting
Range
Unit
Ad
50
Energy saving
operation
1
Manual
-
-
51
Energy saving
amount
30
0
–30
%
5.12.2 Automatic Energy Saving Operation
The amount of energy saving can be automatically calculated based on the rated
motor current (bA.13) and the no-load current (bA.14). From the calculations, the
output voltage can be adjusted.
Group Code
Name
Setting
Setting Range
Unit
Ad
50
Energy saving
operation
2
Auto
-
-
If operation frequency is changed or acceleration and /deceleration is carried out by a stop
command during the energy saving operation, the actual Acc/Dec time may take longer
than the set Acc/Dec time due to the time required to return to the
general
operation from
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...