PID Operation Sleep Mode Setting Details
Code and
Features
Description
AP.37 PID Sleep
DT,
AP.38 PID Sleep
Freq
If an operation frequency lower than the value set at AP.38 is
maintained for the time set at AP.37, the operation stops and the PID
operation sleep mode starts.
AP.39 PID
WakeUp Lev,
AP.40 PID
WakeUp Mod
Starts the PID operation when in PID operation sleep mode. If AP.40 is
set to 0 (Below Level), the PID operation starts when the feedback
variable is less than the value set as the AP.39 parameter setting.
If AP.40 is set to 1 (Above Level), the operation starts when the
feedback variable is higher than the value set at AP.39. If AP.40 is set
to 2 (Beyond Level), the operation starts when the difference between
the reference value and the feedback variable is greater than the value
set at AP.39.
5.8.4 PID Switching (PID Openloop)
When one of the multi-function terminals (In.65
–69) is set to 23 (PID Openloop) and is
turned on, the PID operation stops and is switched to general operation. When the
terminal turns off, the PID operation starts again.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...