Code and
Features
Description
NO/NC Sel
only or to use as NO (Normal Open) and NC(Normal Close). If set to 1:
NO only, the terminal in which the functions are set to Fx/Rx cannot be
set as NC.
If set to 0: NO/NC, terminals set as Fx/Rx can also be set as NC.
In.90 DI Status
Display the configuration of each contact. When a segment is
configured as A terminal using dr.87, the On condition is indicated by
the top segment turning on. The Off condition is indicated when the
bottom segment is turned on. When contacts are configured as B
terminals, the segment lights behave conversely. Terminals are
numbered P1
–P5, from right to left.
Items
Bit On when A contact is
set
Bit Off when A contact is set
Keypad
4.19 Fire Mode Operation
This function is used to allow the inverter to ignore minor faults during emergency
situations, such as fire, and provides continuous operation to fire pumps.
When turned on, Fire mode forces the inverter to ignore all minor fault trips and repeat
a Reset and Restart for major fault trips, regardless of the restart trial count limit.
Fire Mode Parameter Settings
Group Code
Name
Setting
Setting
Range
Unit
Ad
80
Fire Mode selection
1
Fire Mode
0
–2
-
81
Fire Mode frequency
0
–60
0
–60
82
Fire Mode run
direction
0
–1
0
–1
83
Fire Mode operation
count
Not
configurable
-
-
In
65
–69
Px terminal setting
options
51 Fire Mode
0
–52
-
Ad 80. If Fire Mode Sel parameter is selected as Fire Mode and the terminal selected
as 51: Fire Mode in In.65
–69 Px terminal feature setup parameter is entered as On
state, the inverter will operate as Fire Mode and Ad 83. Fire Mode Count will be
increased by 1.
The inverter runs in Fire Mode when Ad. 80 (Fire Mode Sel) is set to Fire Mode Test,
and the multi-function terminal (In. 65-69 Px) configured for the fire mode (51: Fire
Mode) is turned on. But when the minor fault trips are ignored or there are major fault
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...