UNITOUR Power System
User Manual
Page 43
•
To manually enter a network setting tap STATIC IP. Tap
either the “Address”,
“NetMask” or “Gateway” fields and a pop-up keyboard allows you to enter the
required settings. To automatically enter the network settings for Art-Net, tap
SET ART-NET
DEFAULT
Tap
SAVE
to keep your settings and exit.
Note. To use sACN or Art-Net protocols, UNITOUR must have a valid IP address and NetMask
set in order to work correctly. When using Art-Net, it is essential that the IP address is set to
be compatible with the address on the device sending the Art-Net packets.
Streaming ACN utilizes multicasting and as such the actual IP address in use is generally
irrelevant.
3.21.2
Configure Alarms
The “Configure Alarms” menu lists all of the “conditions” that UNITOUR continuously monitors
and allows you to select which conditions will trigger an ALARM or generate an entry into the
UNITOUR LOG or send a message to HOUSTON X or SYSLOG when a change in condition
is detected.
HOUSTON X is LSC’s monitoring software (see section 5) and SYSLOG is a remote logging
system (see section 3.22.3).
Tap
LOG IN
,
ADVANCED
,
SYSTEM SETTINGS
,
CONFIGURE ALARMS
.
Alarm Log
The left-
hand column lists the “Conditions” that UNITOUR monitors. Scroll down to see more
conditions.
•
A green dot indicates that a condition change message will be sent
•
A grey dot indicates that a condition change is ignored
Scroll Bar