7.3 Operating command setting method
Operation via keypad RUN key and STOP/RST key
7.3.1
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
drv
[Drive mode]
0
0 - 4
1
drC
[Direction of motor rotation
select]
-
F, r
F
Set drv
– [Drive mode] to 0.
Acceleration is started upon pressing the Run key while operating frequency is set.
Motor decelerates to stop by pressing the STOP/RST key.
Selecting rotation direction is available at drC -
[Direction of motor rotation select] when operating
command is issued via keypad.
drC
[Direction of motor
rotation select]
F
Forward
r
Reverse
►
When remote keypad is connected, body-embedded
keypad is deactivated.
Operating command via FX, RX terminal 1
7.3.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
drv
[Drive mode]
1
0 - 4
1
I/O group
I17
[Multi-function input
terminal P1 define]
0
0 - 30
0
I18
[Multi-function input
terminal P2 define]
1
0 - 30
1
Set
drv
– [Drive mode] to 1.
Set I17 and I18 to 0 and 1 to use P1 and P2 as FX and RX terminals.
“FX” is Forward run command and “RX” Reverse run.
►
Motor is stopped when FX/RX terminal is
ON/OFF at the same time.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...