Basic Functions
76
Group
Code
Parameter Name
Setting
Unit
I/O group
I 2
[NV input Min voltage]
0
V
I 3
[Frequency corresponding to I 2]
0.00
Hz
I 4
[NV input Max voltage]
10.00
V
I 5
[Frequency corresponding to I 4]
5.00
Hz
I7
[V1 input Min voltage]
0.00
V
I 8
[Frequency corresponding to I 7]
0.00
Hz
I 9
[V1 input max voltage]
10.00
V
I10
[Frequency corresponding to I 9]
5.00
Hz
I12
[I input minimum current]
4.00
mA
I13
[Frequency corresponding to I 12]
0.00
Hz
I14
[I input max current]
20.00
mA
I15
[Frequency corresponding to I 14]
60.00
Hz
After the above setting is made, if 5V is applied to V1 with 12mA given to terminal I,
output frequency would be 32.5Hz. If
–5V is applied to V1 terminal with 12mA given to
terminal I, output frequency would be 27.5Hz.
Frequency setting via 0 - 10[V] + 0 - 20[mA] input
7.1.7
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
6
0 - 8
0
Select 6 in Frq code of Drive group.
Related code: I 6 - I 10, I 11 - I 15
Refer to Frequency setting via -10 - +10V voltage input + 0 - 20mA input.
Frequency setting via RS 485 communication
7.1.8
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
0.0
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
7
0 - 8
0
Select 7 in Frq code of Drive group.
Related code: I 59, I 60, I 61
Refer to Chapter 11. RS485 communication.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...