73
Basic Functions
B
as
ic
Fu
nc
tio
ns
Frequency setting via
–10 - +10[V] input
7.1.3
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
2
0 - 8
0
I/O group
I 2
[NV input minimum voltage]
-
0 - -10
0.0
V
I 3
[Frequency corresponding to
I2]
-
0 - 400
0.00
Hz
I 4
[NV input max voltage]
-
0 - 10
10.00
V
I 5
[Frequency corresponding to
I4]
-
0 - 400
60.00
Hz
I6 - I10
[V1 input]
Set
Frq
– [Frequency Mode] to 2.
The set frequency can be monitored in
0.00
- [Frequency Command].
►
Apply
–10V - +10V signal between V1 and CM terminal.
►
Output frequency corresponding to
–10V - +10V input voltage to V1 terminal
►
I 2 - I 5: Setting input range and corresponding frequency to -10V - 0V V1 input voltage
Ex) when minimum (-) input voltage is -2V with corresponding frequency 10Hz and Max
voltage is
–8V with run freq. 50Hz.
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...