Basic Functions
72
7 Basic Functions
7.1 Frequency mode
Keypad Frequency setting 1
7.1.1
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
0.00
[Frequency Command]
-
0 - 400
0.00
Hz
Frq
[Frequency mode]
0
0 - 8
0
Set
Frq
– [Frequency mode] to 0 {Frequency setting via Keypad 1}.
Set the desired frequency in
0.00
and press the Prog/Ent (
) key to enter the value into
memory.
The value is settable less than
F21
– [Max frequency].
►
When remote keypad is connected, keypad keys on the body are deactivated.
Keypad Frequency setting 2
7.1.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
0.00
[Frequency Command]
-
0 - 400
0.00
Hz
Frq
[Frequency mode]
1
0 - 8
0
Set
Frq
– [Frequency mode] to 1{Frequency setting via Keypad 2}.
In
0.00
, frequency is changed upon pressing the Up (
)/Down (
) key. In this case,
UP/Down keys serve as a potentiometer.
The value is settable less than
F21
– [Max frequency].
►
When remote keypad is connected, keypad keys on the body are deactivated.