35
Programming Keypad & Basic operation
B
a
s
ic
O
p
s
.
Frequency Setting via potentiometer & operating via
4.7.2
terminals
1
Apply AC input power to the inverter.
2
When 0.00 appears Press the Up (
) key four times.
3
Frq is displayed. Frequency setting mode is selectable.
Press the Ent (
) key once.
4
Present setting method is set to 0 (frequency setting via keypad).
Press the Up (
) key three times.
5
After 3 (Frequency setting via potentiometer) is set, press the Ent
(
) key once.
6
Frq is redisplayed after 3 stops blinking.
Press the Down (
) key four times.
Turn the potentiometer to set to 10.00 Hz in either Max or Min
direction.
7
Turn on the switch between P1 (FX) and CM (See Wiring below).
RUN lamp begins to blink with FWD lamp lit and the accelerating
frequency is displayed on the LED.
When run frequency 10Hz is reached, the value is displayed as
shown left.
Turn off the switch between P1 (FX) and CM terminals.
8
RUN lamp begins to blink and decelerating frequency is displayed
on the LED.
When run frequency is reached to 0Hz, Run and FWD lamp turn off
and
10.00
is displayed.
Wiring
Operating pattern
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...