Specifications
200
Environment
13.1.6
Protection degree
IP 20, UL TYPE1 (Ambient Temperature 40
C) 2)
Ambient temp
-10
C - 50
C
Storage temp
-20
C - 65
C
Humidity
Below 90% RH (no condensation)
Altitude/Vibration
Below 1,000m, 5.9m/sec2 (0.6G)
Atmospheric pressure
70-106 kPa
Location
Protected from corrosive gas, combustible gas, oil mist or dust
2) UL TYPE1 with top cover and conduit box installed.
13.2 Temperature Derating Information
Load and ambient temperature classified by the Carrier Frequency
1) The above graph is only applied when the inverter is operated in the allowable temperature.
Pay attention to the air cooling when the inverter is installed in a panel box, and the inside
temperature should be within an allowable temperature range.
2) This derating curve is based on inverter current rating when rated motor is connected
% of Drive
Rated Amps
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0
Carrier Frequency in kHz
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
72%
58%
40℃ Rating
41℃ - 50℃ Rating
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...