Advanced functions
118
8.13 Relay On/Off Control
If the analog input value is over the set value, the output relay or multi-function output
terminal can be turned ON or OFF. Select the analog input to use for ON/OFF control at
F72 and set the levels at which the output terminal is ON and OFF at F73, 74 respectively. If
the analog input value is over the value set at F73, the output terminal is ON and if below
F74, it is OFF.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F72
OnOff Ctrl Src
-
0: None
1: V
2: I
0
F73
On-Ctrl Level
-
0.00-100.00[sec]
90.00
sec
F74
Off-Ctrl Level
-
0.00-100.00[sec]
10.00
sec
I/O
group
I54-55 Relay Define x
-
19. OnOffControl
0.00
8.14 Power On Run Delay
After Run command is applied by the terminals, the inverter will operate after the time
set in F06_Power-on run has exceeded.
This function can be applied for lubrication purpose in applications such as mining or
oil systems.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function
group 1
F5
Power On Run
-
0 : NO
1 : YES
0 : NO
F6
Run Delay Time
-
0-6000[sec]
0
sec
Summary of Contents for SV-iG5H Series
Page 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Page 14: ......
Page 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Page 24: ...10 Installation Wiring ...
Page 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Page 174: ...Protective functions 160 ...
Page 220: ...206 DECLARATION OF CONFIRMITY ...
Page 224: ...210 ...