Advanced functions
109
A
dv
an
ce
d
Fu
nc
tio
ns
Sleep & Wake-up
8.7.2
In the night for example, if output frequency of PID control is maintained over sleep
delay time(A1) due to not enough flux, Sleep function becomes sleep mode
automatically and inverter is stop. Under sleep mode, if error of PID Reference and
Feedback is over A6(Wake-up Level), Sleep mode is released and the inverter restarts.
If stop command is input, Sleep mode is released
Sleep Boost
8.7.3
Before going into sleep mode, the inverter additionally operates to increases feedback
pressure.
This extends the time in which the motor is stopped that can avoid frequent start/stop.
Group
Code
Parameter Name
Setting
Range
Default
Unit
Application
group
A 1 Sleep Delay
-
0-6000.0
20.0
sec
A 2 Sleep Freq.
-
0-Max Freq.
0.00
Hz
A 3 Sleep Boost Set
-
0.0-100.0
0.00
%
A 4 Sleep Boost Time
-
0-6000.0
0.0
sec
A 5 Wake-up Delay Time
-
0-6000.0
20.0
sec
A 6 Wake-up Level
-
0.0-100.0
20.0
%