Basic Functions
92
7.6 Stop method select
Decel to stop
7.6.1
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function group 1
F4
[Stop mode select]
0
0 - 3
0
Select 0 {decel to stop} in F4 code.
Motor decelerates to 0 Hz and stops during the setting time.
DC braking to stop
7.6.2
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function group 1
F4
[Stop mode select]
1
0 - 3
0
Select 1 {DC brake to stop} in F4 code.
Refer to page 95.
Free run stop
7.6.3
Group
Code
Parameter Name
Setting
Range
Default
Unit
Function group 1
F4
[Stop mode select]
2
0 - 3
0
Select 2 {Free run stop} in F4 code.
When operating command is turned OFF, Output Frequency and voltage are shut down.