Chapter 11. Troubleshooting
11
-
13
(continued)
Error
Code
Error
CPU state
Message
Cause
Corrective Actions
0026h
FMM 3 Parameter
Error
Stop
FMM 3 PARA Error
FMM 3 Parameter Error
Correct the parameter.
0030h
Operation Error
Stop
Operation Error
•
A digit of other than 0 to 9 has met
during BCD conversion.
•
An operand value is outside the
defined operand range.
Correct the content of the
error step.
0031h WDT
Over
Continue
(stop)
WDT Over Error
Scan time has overrun the watch dog
time.
Check the maximum scan
time of the program and
modify the program or
insert programs.
0032h
Error of Program
Change during
run.
Stop
PGM Change Error
An error has occurred at program
change during run. (NO SBRT, JME
and END …)
Program replacement has
not been completed during
run. (JMP ~ JME, FOR ~
NEXT, CALLx and SBRTx
…)
0033h
Program Check
Error
Continue
Code Check Error
An error has occurred while checking
a program.
Correct the error.
0040h
Code Check Error Stop
Code Check Error
An instruction unreadable by the CPU
is included.
Correct the error step.
0041h
Missing the END
instruction in the
program.
Stop
Miss END Error
The program does not have the END
instruction.
Insert the END instruction
at the bottom of the
program.
0042h
Missing the RET
instruction in the
program.
Stop
Miss RET Error
The subroutine does not has the RET
instruction at its bottom.
Insert the END instruction
at the bottom of the
program.
0043h
Missing the SBRT
instruction in the
subroutine
program.
Stop
Miss SBRT Error
The subroutine does not has the
SBRT instruction.
Insert the SBRT
instruction.
0044h
The JMP ~ JME
instruction error
Stop
JMP(E) Error
The JMP ~ JME instruction error
Correct the JMP ~ JME
instruction.
0045h
The FOR ~ NEXT
instruction error
Stop
FOR~NEXT Error
The FOR ~ NEXT instruction error
Correct the FOR ~ NEXT
instruction.
0046h
The MCS ~
MCSCLR
instruction error
Stop
MCS~MCSCLR
Error
The MCS ~ MCSCLR instruction error
Correct the MCS ~
MCSCLR instruction.
0047h
The MPUSH ~
MPOP instruction
error
Stop
MPUSH ~ MPOP
Error
The MPUSH ~ MPOP instruction error
Correct the MPUSH ~
MPOP instruction
0048h
Dual coil error
Stop
DUAL COIL Error
Timer or counter has been duplicated. Correct timer, counter.
0049h
Syntax error
Stop
Syntax Error
Input condition error, or too much use
of LOAD or AND(OR) LOAD.
Check and correct the
program.
0050h
Battery error
Continue
Battery Error
Backup battery voltage error
Replace the battery under
the present condition.