Communication Function
358
11.9
Communication Frame Monitoring
You can easily monitor the status (normal, CRC/Checksum error, other errors, etc.) of the
communication frame being received from the master by using the keypad.
Group
Code
LCD Display
Setting Display
Unit
COM
90
Comm Mon Sel
0
Int 485
-
91
Rcv Frame Num
-
-
-
92
Err Frame Num
-
-
-
93
NAK Frame Num
-
-
-
94
Comm Update
0
-No-
-
1
-Yes-
Communication Frame Monitoring Details
Code
Description
COM-90 Comm Mon Sel
Selects the communication channel to monitor.
COM-91 Rcv Frame Num
Counts the number of communication frames received normally
from the master device.
COM-92 Err Frame Num
Counts the number of CRC errors when the Modbus-RTU is set and
counts Checksum errors when the LS Inv 485 is set.
COM-93 NAK Frame Num
Counts the number of errors (communication address errors, data
range errors, writing prohibition errors) that occur in the
communication frames received from the master device.
COM-94 Comm Update
Reconnects the communication after the initial status parameter is
changed to communication speed (baud rate), etc.
11.10
Special communication Area Settings
The following table lists the memory map of the entire memory addresses used for network
communication in the iS7 series inverters.
Communication Area
Memory Map
Description
Common iS5 compatible
0h0000 - 0h00FF
Area compatible with iS5
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...