Using Protection Features
324
10
Using Protection Features
Protection features provided by the SV-iS7 series inverter are categorized into two types:
Protection from damage due to an overheating motor and Protection against inverter
malfunction.
10.1
Motor Protection
10.1.1
Electrothermal Motor Overheating Prevention (ETH)
ETH is a protective function that uses the output current of an inverter without a separate
temperature sensor to predict increases in motor temperature and protect the motor, based
on its heat characteristics.
Group Code
LCD Display
Parameter Setting
Setting Range
Unit
PRT
40
ETH Trip Sel
0
None
None/Free-Run/Dec
-
41
Motor Cooling
0
Self-cool
-
-
42
ETH 1min
-
150
120-200
%
43
ETH Cont
-
120
50
–
180
%
Electronic Thermal (ETH) Prevention Function Setting Details
Code
Description
PRT-40 ETH Trip Sel
ETH can be selected to provide motor thermal protection. The LCD screen
displays
”E
-
Thermal.”
Setting
Function
0 None
The ETH function is not activated.
1 Free-Run
The inverter output is blocked. The motor coasts to a
halt (free-run).
2 Dec
The inverter decelerates the motor to a stop.
PRT-41 Motor
Cooling
Select the drive mode of the cooling fan, attached to the motor.
Setting
Function
0 Self-cool
As the cooling fan is connected to the motor axis, the
cooling effect varies based on motor speed. Most
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...