Using Monitor Functions
9.3.2
Current Output (4
–
20 mA)
Select the items to be output from AO2 (Analog Output 2) terminal of the inverter terminal
block and adjust the output sizes.
Group
Code
LCD Display
Parameter Setting
Unit
OUT
07
AO2 Mode
0
Frequency
-
08
AO2 Gain
-
80.0
%
09
AO2 Bias
-
20.0
%
10
AO2 Filter
-
5
ms
11
AO2 Const %
-
0.0
%
12
AO2 Monitor
-
0.0
%
Current Output Setting Details
Code
Description
OUT-07 AO2
Mode
Select the output types.
Setting
Description
0
Frequency
Outputs an operation frequency as the standard. A 10 V
output is supplied based on the frequency set at DRV-20
(Max Freq).
1
Output
Current
A 10 V output is supplied from 200% of the inverter-rated
current (based on CT: Constant Torque).
2
Output
Voltage
Sets the outputs based on the inverter output voltage. A 10
V output is supplied from the voltage set at BAS-15 (Rated
V).
If 0 V is set at BAS-15, 200 V/400 V models output 10 V
based on the actual input voltage (220 V and 440 V
respectively).
3
DC Link
Volt
Outputs the inverter DC link voltage as the standard.
Outputs 10 V when the DC link voltage is 410 VDC for 200 V
models, and 820 VDC for 400 V models.
4
Torque
Outputs the generated torque as the standard. Outputs 10
V at 250% of the motor-rated torque.
5
Output
Power
Monitors the output wattage. 200% of the rated output is
the maximum display voltage (10 V).
6
Idse
Outputs the maximum voltage at 200% of the no load
current.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...