Learning Advanced Features
Adv
anc
ed
Feat
ur
es
273
Code
Description
CNF-60 Add Title UP
When the inverter SW version is updated and more code is added, CNF-
60 settings will add, display, and operate the added codes. Set CNF-60
to “1 (Yes)” and disconnect the keypad from the inverter. Reconnecting
the keypad to the inverter updates titles.
CNF-62 WH Count Reset Initialize the accumulated electrical energy consumption count.
CNF-74 Fan Time
Displays the accumulated cooling fan operation time.
CNF-75 Fan Time Rst
Initialize the accumulated cooling fan operation time at CNF-74.
8.34
Timer Settings
Set a multi-function input terminal to a timer and set the On/Off controls to the multi-function
outputs and relays according to the timer settings.
Group Code Name
LCD Display
Parameter
Setting
Setting
Range
Unit
IN
65
–
75
Px terminal
configuration
Px Define (Px: P1
–
P8 [optional: P9
–
P11])
38 Timer In
-
-
OUT
31
Multi-function relay 1 Relay 1
28 Timer Out -
sec
33
Multi-function output 1 Q1 Define
55
Timer on delay
TimerOn Delay
0.00
0.00
–
100.00 sec
56
Timer off delay
TimerOff Delay
0.00
0.00
–
100.00 sec
Timer Setting Details
Code
Description
IN-65
–
75 Px Define
Selects one of the multi-function input terminals and change it to a timer
terminal by setting it to “38 (Timer In)”.
OUT-31 Relay 1,
OUT-36 Q1 Define
Sets the multi-function output terminal or relay to be used as a timer to
“28 (Timer out)”.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...