10
2.4
Input and Output Specifications 400 V Class (30
–
160 kW)
Model SV xxx iS7
–
2x
0300 0370 0450 0550 0750 0900 1100 1320 1600
Applied
Motor
Normal load
HP
50
60
75
100 125 150 200 250 300
kW
37
45
55
75
90
110 132 160 185
Heavy load
HP
40
50
60
75
100 125 150 200 250
kW
30
37
45
55
75
90
110 132 160
Rated
output
Rated Capacity
(kVA)
46
57
69
84
116 139 170 201 248
Rated
Current
(A)
Normal
load
75
91
110 152 183 223 264 325 370
Heavy
load
61
75
91
110 152 183 223 264 325
Output Frequency
0
–
400 Hz (Sensorless-1: 0
–
300 Hz, Sensorless-2, Vector: 0.1
–
120
Hz)
Output Voltage (V)
3-Phase 380
–
480 V
Rated
input
Working Voltage (V) 3-Phase 380
–
480 VAC (-15%
–
+10%)
Input Frequency
50
–
60 Hz (
5%)
Rated
Current
(A)
Normal
load
67.5 81.7 101.8 143.6 173.4 212.9 254.2 315.3 359.3
Heavy
load
55.5 67.9 82.4 102.6 143.4 174.7 213.5 255.6 316.3
•
The standard used for 400 V inverters is based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at CON-04.
•
The output frequency is limited to 0
–
300 Hz if DRV-09 (control mode) is set to
“
3
(Sensorless-1),
”
and to 0
–
120 Hz if DRV-09 (control mode) is set to
“
4 (Sensorless-3).
”
•
The maximum output voltage cannot exceed the input voltage of the power source.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...