Technical Specifications
9
2.3
Input and Output Specifications 400 V Class (0.75
–
22 kW)
Model SV xxx iS7
–
2x
0008 0015 0022 0037 0055 0075 0110 0150 0185 0220
Applied
Motor
Normal load
HP
2
3
5
7.5
10
15
20
25
30
40
kW
1.5
2.2 3.7
5.5
7.5
11
15
18.5 22
30
Heavy load
HP
1
2
3
5
7.5
10
15
20
25
30
kW
0.75 1.5 2.2
3.7
5.5
7.5 11
15
18.5 22
Rated
output
Rated Capacity
(kVA)
1.9
3.0 4.5
6.1
9.1
12.2 18.3 22.9 29.7 34.3
Rated
Current
(A)
Normal
load
4
6
8
12
16
24
30
39
45
61
Heavy
load
2.5
4
6
8
12
16
24
30
39
45
Output Frequency
0
–
400 Hz (Sensorless-1: 0
–
300Hz, Sensorless-2, Vector: 0.1
–
120Hz)
Output Voltage (V)
3-Phase 380
–
480 V
Rated
input
Working Voltage (V) 3-Phase 380
–
480 VAC (-15%
–
+10%)
Input Frequency
50
–
60 Hz (
5%)
Rated
Current
(A)
Normal
load
3.7
5.7 7.7
11.1 14.7 21.9 26.4 35.5 41.1 55.7
Heavy
load
2.2
3.6 5.5
7.5 11.0 14.4 22.0 26.6 35.6 41.6
•
Only the heavy duty ratings apply to model types without a built-in DC resistor (NON- DCR).
•
The standard motor capacity is based on a standard 4-pole motor.
•
The standard used for 400 V inverters is based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at CON-04.
•
The output frequency is limited to 0-300 Hz if DRV-09 (control mode) is set to
“
3 (Sensorless-
1),
”
and to 0-120 Hz if DRV-09 (control mode) is set to
“
4 (Sensorless-3).
”
•
The maximum output voltage cannot exceed the input voltage of the power source.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...