Learning Advanced Features
Adv
anc
ed
Feat
ur
es
213
Group Code Name
LCD Display
Parameter Setting
Setting Range Unit
current
14
Motor no-load
current
Noload Curr
1.6 (0.75 kW based) 0.5
–
1000
A
16
Motor efficiency Efficiency
72 (0.75 kW based) 70
–
100
%
17
Load Inertia ratio Inertia Rate
0 (0.75 kW based)
0
–
8
-
ADV
92
SlipGain Mot-H
SlipGain Mot-H 50
0-200
%
93
SlipGain Gen-H
SlipGain Gen-H 50
0-200
%
94
SlipGain Mot-L
SlipGain Mot-L 50
0-200
%
95
SlipGain Gen-L
SlipGain Gen-L 50
0-200
%
96
Slip Filter
Slip Filter
300
0-10000
msec
97
Slip Comp Freq
Slip Comp Freq 5.00
0-60.00
Hz
98
Slip Gain Freq
Slip Gain Freq
9.00
0-20.00
Hz
Slip Compensation Operation
–
Setting Details
Code
Description
DRV-09 Control Mode
Sets DRV-
09 to “2 (Slip Compen)” to carry out the slip compensation
operation.
DRV-14 Motor Capacity Sets the capacity of the motor connected to the inverter.
BAS-11 Pole Number
Enters the number of poles from the motor rating plate.
BAS-12 Rated Slip
Enters the number of rated rotations from the motor rating plate.
BAS-13 Rated Curr
Enters the rated current from the motor rating plate.
BAS-14 Noload Curr
Enters the measured current when the load on the motor axis is
removed and when the motor is operated at the rated frequency. If the
no-load current is difficult to measure, enter a current equivalent to 30-
50% of the rated motor current.
BAS-16 Efficiency
Enters the efficiency from the motor rating place.
BAS-17 Inertia Rate
If inertia rate < 10 x motor inertia, set BAS-16 to
“
0
”
.
If inertia rate = 10 x motor inertia, set BAS-16 to
“
1
”
.
If inertia rate > 10 x motor inertia, set BAS-16 to
“
2
–
8
”
.
ADV-92 Slip Gain Mot-H
ADV-93 Slip Gain Gen-H
This is the slip compensation gain used in the region where the output
frequency is higher than the slip compensation gain switching frequency
(ADV-98). You can set the gain values differently for the
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...