Learning Advanced Features
Adv
anc
ed
Feat
ur
es
201
8.2
Jog Operation
The jog operation allows for temporary control of the inverter. You can enter a jog operation
command using the multi-function terminals.
The jog operation is the second-highest priority operation, after the dwell operation. If a jog
operation is requested while operating the multi-step, up-down, or 3-wire operation modes,
the jog operation overrides all other operation modes.
8.2.1
Jog Operation 1-Forward Jog via Multi-function Terminal
The jog operation is available using the multi-function terminal input. To start a forward jog
operation, an Fx operation command must be entered. The table below lists parameter
settings for a forward jog operation using the multi-function terminal input.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
DRV
11
Jog frequency
JOG Frequency
10.00
0.5
–
Max Freq Hz
12
Jog operation
acceleration time
JOG Acc Time
20.00
0.00
–
600.00
sec
13
Jog operation
deceleration time JOG Dec Time
30.00
0.00
–
600.00
sec
IN
65
–
75
Px terminal
configuration
Px Define(Px:
P1
–
P8 [optional:
P9
–
P11])
6
JOG
-
-
Forward Jog Details
Code
Description
IN-65
–
75 Px Define
Select an input terminal from IN-65
–
75 (P1
–
P8 [optional: P9-P11]) and set
it to
“6
(Jog)
”
.
[Terminal settings for jog operation using the P5 terminal]
DRV-11 JOG Frequency Sets the operation frequency.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...