Basic Functions
182
If the torque boost amount is set too large, overheating of the motor due to over-excitation will
occur.
7.15
Output Voltage Setting
Output voltage settings are required when a motor’s rated voltage differs from the input
voltage to the inverter. Set BAS-
15 to configure the motor’s rated operating voltage. The set
voltage becomes
the output voltage of the inverter’s base frequency. When the inverter
operates above the base frequency, and when the motor’s voltage rating is lower than the
input voltage at the inverter, the inverter adjusts the voltage and supplies the motor with the
voltage set at BAS-15 (motor-
rated voltage). If the motor’s rated voltage is higher than the input
voltage at the inverter, the inverter will supply the inverter input voltage to the motor.
If BAS-15 (motor-
rated voltage) is set to “0,” the inverter correc
ts the output voltage based on
the input voltage in the stopped condition. If the frequency is higher than the base frequency
andwhen the input voltage is lower than the parameter setting, the input voltage will be the
inverter output voltage.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
BAS
15
Motor rated voltage Rated Volt
220
0, 180
–
480
V