Basic Functions
179
B
as
ic
Func
tio
ns
7.14
Torque Boost
7.14.1
Manual Torque Boost
Manual torque boost enables users to adjust the output voltage during low-speed operation or
motor start. You can increase the low-speed torque or improve motor-starting properties by
manually increasing the output voltage. Configure the manual torque boost while running
loads that require a high starting torque, such as lift-type loads.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
DRV
15
Torque boost options
Torque
Boost
0 Manual
0
–
1
-
16
Forward torque boost Fwd Boost* 2.0
0.0
–
15.0
%
17
Reverse torque boost
Rev Boost*
2.0
0.0
–
15.0
%
* For 90 kW
–
160 kW model types, the default setting value is 1.0 [%].
Manual Torque Boost Setting Details
Code
Description
DRV-16 Fwd Boost
Sets the torque boost for forward operation.
DRV-17 Rev Boost
Sets the torque boost for reverse operation.
Output Voltage = Output voltage affected by DRV-16,17 Manual torque boost parameter
= V/F v Boost
ed
voltage
=
(𝑀𝑎𝑥𝑖𝑚𝑢𝑚 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 – 𝐵𝑜𝑜𝑠𝑡𝑒𝑑 𝑣𝑜𝑙𝑡𝑎𝑔𝑒) ×
𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝑓𝑟𝑒𝑞𝑢𝑒𝑛𝑐𝑦
𝐵𝑎𝑠𝑒 𝑓𝑟𝑒𝑞𝑢𝑒𝑛𝑐𝑦
+ 𝐵𝑜𝑜𝑠𝑡𝑒𝑑 𝑣𝑜𝑙𝑡𝑎𝑔𝑒