Basic Functions
157
B
as
ic
Func
tio
ns
7.5
Command Source Configuration
Various devices can be selected as command input devices for the iS7 inverter. Input devices
available include the keypad, multi-function input terminal, RS-485 communication, and field
bus adapter.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
06
Command Source Cmd Source
0
Keypad
0
–
5
-
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Field Bus
5
PLC
7.5.1
The Keypad as a Command Input Device
Set DRV-
06 to “0 (Keypad)” to select the keypad as the command source
.
Since the keypad is now the command source, forward or reverse operation starts when the
[FWD] or [REV] key is pressed, and it stops when the [STOP/RESET] key is pressed.
Group Code
Name
LCD Display
Parameter Setting
Setting Range Unit
DRV
06
Command source Cmd Source
0
KeyPad
0
–
5
-
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...