Troubleshooting
189
Warning Messages
Keypad
Display
LCD Display
Description
Over Load
Displayed when the motor is overloaded. Operates when Pr.17 is
set to 1. To operate, select 5. Set the digital output terminal or
relay (OU.31 or OU.33) to 5 (Over Load) to receive overload
warning output signals.
Under Load
Displayed when the motor is underloaded. Operates when Pr.25
is set to 1. Set the digital output terminal or relay (OU.31 or
OU.33) to 7 (Under Load) to receive underload warning output
signals.
INV Over
Load
Displayed when the overload time equivalent to 60% of the
inverter overheat protection (inverter IOLT) level, is accumulated.
Set the digital output terminal or relay (OU.31 or OU.33) to 6 (IOL)
to receive inverter overload warning output signals.
Lost
Command
Lost command warning alarm occurs even with Pr.12 set to 0.
The warning alarm occurs based on the condition set at Pr.13- 15.
Set the digital output terminal or relay (OU.31 or OU.33) to 13
(Lost Command) to receive lost command warning output signals.
If the communication settings and status are not suitable for P2P,
a Lost Command alarm occurs.
Fan
Warning
Displayed when an error is detected from the cooling fan while
Pr.79 is set to 1. Set the digital output terminal or relay (OU.31 or
OU.33) to 8 (Fan Warning) to receive fan warning output signals
DB
Warn %ED
Displayed when the DB resistor usage rate exceeds the set value.
Set the detection level at Pr.66.
Retry Tr
Tune
Tr tune error warning alarm is activated when Dr.9 is set to 4. The
warning alarm occurs when the motor’s rotor time constant (Tr) is
either too low or too high.
PID
Sleep
When the PID operation enters sleep mode, a warning occurs.
olw
ulw
iolw
lcw
fanw
dbw
trer
slp
Summary of Contents for LSLV-S100 Series
Page 1: ......
Page 11: ...Preparing the Installation 2 ...
Page 13: ...Preparing the Installation 4 5 5 22kW 3 Phase ...
Page 16: ...Preparing the Installation 7 Front cover removed ...
Page 45: ...Installing the Inverter 36 IP66 0 4 0 8kW 3 phase 1 5 2 2kW 3 phase ...
Page 50: ...Installing the Inverter 41 0 4 22kW Standard I O Multiple I O ...
Page 67: ...Installing the Inverter 58 ...
Page 69: ...Learning to Perform Basic Operations 60 30 75kW Models ...
Page 193: ...Table of Functions 184 ...
Page 205: ...196 Troubleshooting ...
Page 228: ...Technical Specification 219 30 75kW Models 30 kW 3 Phase 37 45 kW 3 Phase ...
Page 230: ...Technical Specification 221 IP66 Models 0 4 4 0kW NP Non PDS type ...
Page 231: ...Technical Specification 222 0 4 4 0kW PDS type ...
Page 233: ...Technical Specification 224 5 5 7 5kW NP Non PDS type ...
Page 235: ...Technical Specification 226 11 0 22 0kW NP Non PDS type ...
Page 259: ...250 ...
Page 261: ...252 ...
Page 263: ...254 ...