10.4 Peripheral devices
Compatible circuit breakers, leakage circuit breakers, and
magnetic contactors (manufactured by LS Electric)
Product (kW)
Circuit breaker
Leakage circuit breaker Magnetic contactor
Model
Rated
current
Model
Rated
current
Model
Rated
current
3-Phase
400 V
5.5
TD125U
30A
EBS 33b
30A
MC-32a
32A
7.5
30A
30A
MC-32a
32A
11
50A
EBS 53b
50A
MC-40a
40A
15
60A
EBS 103b
60A
MC-50a
50A
18.5
80A
80A
MC-65a
65A
22
100A
100A
The drive is suitable for use in a circuit capable of delivering no more than 35 kA
rms symmetrical amperes at the drive maximum rated voltage, if it is protected
with the recommended circuit breaker.
10.5 Fuse and reactor specifications
Products (kW)
Model type
AC input fuse
AC reactor
DC reactor
Current
Voltage
Inductance Current Inductance Current
3-
Phase
400 V
5.5
LSLV055L100-4
32 A
600 V
1.12 mH
19 A
3.20 mH
17 A
7.5
LSLV075L100-4
35 A
0.78 mH
27 A
2.50 mH
25 A
11
LSLV110L100-4
50 A
0.59 mH
35 A
1.90 mH
32 A
15
LSLV150L100-4
63 A
0.46 mH
44 A
1.40 mH
41 A
18.5
LSLV185L100-4
70 A
0.40 mH
52 A
1.00 mH
49 A
22
LSLV220L100-4
100 A
0.30 mH
68 A
0.70 mH
64 A
The peripheral devices cannot be used if the symmetrical current exceeds 35 kA
at the drive maximum rated voltage.