Technical specifications
368
10 Technical specifications
10.1 Input and output specifications
LSLV[][][][]L100-4NNFN
0055
0075
0110
150
0185
0220
Motor capacity
HP
7.5
10
15
20
25
30
kW
5.5
7.5
11
15
18.5
22
Rated
output
Rated power (kVA)
9.1
12.2
18.3
22.9
29.7
34.3
Rated current (A)
12
16
24
30
39
45
Output speed
Induction motor: 0–3600 (rpm)
Synchronous motor: 0–680 (rpm)
Output voltage (V)
0-380 V (480 V)
Rated
input
Working voltage (V)
3-Phase 380–480 VAC (-10%–+10%)
Input frequency
50–60 Hz (
±
5%)
Rated current (A)
12.9
17.5
26.5
33.4
43.6
50.7
Weight (lbs. [kg])
7.3
[3.3]
7.5
[3.4]
10.2
[4.6]
10.6
[4.8]
16.6
[7.5]
17.7
[8.0]
•
The standard motor capacity is based on a standard 4-pole motor.
•
400 V inverters are designed for a 440 V supply voltage.
•
The maximum output voltage cannot exceed the input voltage.
•
If the input voltage is greater than 480 V, apply input voltage derated by 10%
from the rated input voltage. Also, install an AC reactor in the power input side
if the voltage imbalance between the phases is greater than 2%. [Voltage
imbalance [%] = Max voltage [V] - Min voltage [V] / Three-phase average
voltage [V] x 67 (IEC 61800-3 (5.2.3)]