197
Learning Advanced Features
•
If the pump clean operation is configured for terminal input and it is turned on, and if ADV-
10 (PowerOn Resume) is set to ‘Yes’, a pump clean operation is performed when the
inverter is turned on.
•
When performing a pump clean operation via terminal input,
-
if the terminal input is turned off instantly after it is turned on (the operation is
triggered), 1 pump clean cycle is operated.
-
if ADV-
10 (PowerOn Resume) is set to ‘Yes’, and the terminal input is turned off
instantly after it is turned on (the operation is triggered), and if the inverter is turned
off during a pump clean then is turned back on again, the pump clean operation is
not resumed (because the input terminal is not on when the inverter is turned on).
-
if the terminal input is kept on after it is initially turned on, 1 pump clean cycle is
operated.
5.15 Start & End Ramp Operation
This function is used to rapidly accelerate the pump to the normal operating level, or to
rapidly decelerate the pump and stop it. Start & End ramp operation is performed when
ADV-
24 (Freq Limit) is set to ‘1 (Yes).’
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
AP2
40
Start & End
Ramp Gradient
Start&End
Ramp
0: No
0
No
-
1
Yes
41
StartRampAcc
StartRampAcc
10.0
0
–600.0
Sec
42
EndRampDec
EndRampDec
10.0
0
–600.0
Sec
ADV
24
Frequency limit
options
Freq Limit
0: No
0
No
-
1
Yes
25
Low Freq
minimum value
Freq Limit Lo
30.00
Start Freq
–
Max Freq
Hz
26
Low Freq
maximum value
Freq Limit Hi
60.00
Freq Limit
Lo
–Max Freq
Hz
Start & End Ramp Operation Setting Details
Code
Description
AP2-40 Start&End
Ramp
Sets the pump Start & End Ramp options.
Setting
Function
0
No
The Start & End Ramp operation is not used.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...