Preparing the Installation
14
1.5 Cable Selection
When you install power and signal cables in the terminal blocks, only use cables that meet
the required specification for the safe and reliable operation of the product. Refer to the
following information to assist you with cable selection.
•
Wherever possible use cables with the largest cross-sectional area for mains power wiring,
to ensure that voltage drop does not exceed 2%.
•
Use copper cables rated for 600 V, 75
℃
for power terminal wiring.
•
Use copper cables rated for 300 V, 75
℃
for control terminal wiring.
•
The inverters in the range between 15 and 90 kW must be grounded conveniently with
fixed connections.
•
The inverters in the range between 5,5kW and 11kW must be grounded with and
industrial connector according to IEC 60309.
•
The minimum size of the protective earthing conductor shall comply with the local
safety regulations for high protective earthing conductor current equipment.
•
Only one conductor per terminal should be simultaneously connected
Ground Cable and Power Cable Specifications
Load (kW)
Ground Wire
Input/Output Power Wire
mm
2
AWG
mm
2
AWG
R/S/T
U/V/W
R/S/T
U/V/W
3-Phase
200 V
0.75
3.5
12
1.5
1.5
16
16
1.5
2.2
3.7
2.5
2.5
14
14
5.5
10
10
4
4
12
12
7.5
6
6
10
10
11
10
10
8
8
15
14
6
16
16
6
6
18.5
25
22
4
4
3-Phase
400 V
0.75
2
14
1.5
1.5
16
16
1.5
2.2
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...